Table 323: B16I Output signals
Name Type Description
OUT INTEGER Output value
11.5.5 Settings
The function does not have any parameters available in local HMI or Protection and
Control IED Manager (PCM600)
11.5.6 Monitored data
Table 324: B16I Monitored data
Name Type Values (Range) Unit Description
OUT INTEGER - - Output value
11.5.7 Operation principle
The Boolean 16 to integer conversion function (B16I) will transfer a combination of up to
16 binary inputs INx, where 1≤x≤16, to an integer. Each INx represents a value according
to the table below from 0 to 32768. This follows the general formula: INx = 2
x-1
where
1≤x≤16. The sum of all the values on the activated INx will be available on the output
OUT as a sum of the integer values of all the inputs INx that are activated. OUT is an
integer. When all INx (where 1≤x≤16) are activated, that is = Boolean 1, it corresponds to
that integer 65535 is available on the output OUT. The B16I function is designed for
receiving up to 16 booleans input locally. If the BLOCK input is activated, it will freeze
the output at the last value.
Values of each of the different OUTx from function block B16I for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT
on the function block B16I
Name of input
Type Default Description Value when
activated
Value when
deactivated
IN1 BOOLEAN 0 Input 1 1 0
IN2 BOOLEAN 0 Input 2 2 0
IN3 BOOLEAN 0 Input 3 4 0
IN4 BOOLEAN 0 Input 4 8 0
IN5 BOOLEAN 0 Input 5 16 0
IN6 BOOLEAN 0 Input 6 32 0
Table continues on next page
1MRK 511 287-UUS A Section 11
Logic
403
Technical manual