12.18.2 Functionality
The circuit breaker condition monitoring function SSCBR is used to monitor different
parameters of the circuit breaker. The breaker requires maintenance when the number of
operations has reached a predefined value. For proper functioning of the circuit breaker,
it is essential to monitor the circuit breaker operation, spring charge indication, breaker
wear, travel time, number of operation cycles and accumulated energy. The energy is
calculated from the measured input currents as a sum of I
^
2 t values. Alarms are generated
when the calculated values exceed the threshold settings.
The function contains a block alarm functionality.
The supervised and presented breaker functions include
breaker open and close travel time
spring charging time
number of breaker operations
accumulated I
Y
t per phase with alarm and lockout
remaining breaker life per phase
breaker inactivity
12.18.3 Function block
ANSI10000281-1-en.vsd
SSCBR
I3P*
BLOCK
BLK_ALM
POSOPEN
POSCLOSE
ALMPRES
LOPRES
SPRCHRGN
SPRCHRGD
CBCNTRST
IACCRST
SPCHTRST
TRVTRST
TRVTOAL
TRVTCAL
SPRCHRAL
OPRALM
OPRLOALM
IACCALM
IACCLOAL
CBLIFEAL
NOOPRALM
PRESALM
PRESLO
CBOPEN
CBINVPOS
52a
ANSI10000281 V1 EN
Figure 230: SSCBR function block
1MRK 511 287-UUS A Section 12
Monitoring
525
Technical manual