Table 189: LOCREM Output signals
Name Type Description
OFF BOOLEAN Control is disabled
LOCAL BOOLEAN Local control is activated
REMOTE BOOLEAN Remote control is activated
VALID BOOLEAN Outputs are valid
10.3.6.5 Settings
Table 190: LOCREM Non group settings (basic)
Name Values (Range) Unit Step Default Description
ControlMode Internal LR-switch
External LR-switch
- - Internal LR-switch Control mode for internal/external LR-switch
10.3.7 Local remote control LOCREMCTRL
10.3.7.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Local remote control LOCREMCTRL - -
10.3.7.2 Functionality
The signals from the local HMI or from an external local/remote switch are applied via the
function blocks LOCREM and LOCREMCTRL to the Bay control QCBAY function
block. A parameter in function block LOCREM is set to choose if the switch signals are
coming from the local HMI or from an external hardware switch connected via binary
inputs.
Section 10 1MRK 511 287-UUS A
Control
258
Technical manual