13.2.4 Signals
Table 453: ETPMMTR Input signals
Name
Type Default Description
P REAL 0 Measured active power
Q REAL 0 Measured reactive power
STACC BOOLEAN 0 Start to accumulate energy values
RSTACC BOOLEAN 0 Reset of accumulated enery reading
RSTDMD BOOLEAN 0 Reset of maximum demand reading
Table 454: ETPMMTR Output signals
Name Type Description
ACCST BOOLEAN Start of accumulating energy values
EAFPULSE BOOLEAN Accumulated forward active energy pulse
EARPULSE BOOLEAN Accumulated reverse active energy pulse
ERFPULSE BOOLEAN Accumulated forward reactive energy pulse
ERRPULSE BOOLEAN Accumulated reverse reactive energy pulse
EAFALM BOOLEAN Alarm for active forward energy exceed limit in set
interval
EARALM BOOLEAN Alarm for active reverse energy exceed limit in set
interval
ERFALM BOOLEAN Alarm for reactive forward energy exceed limit in set
interval
ERRALM BOOLEAN Alarm for reactive reverse energy exceed limit in set
interval
EAFACC REAL Accumulated forward active energy value
EARACC REAL Accumulated reverse active energy value
ERFACC REAL Accumulated forward reactive energy value
ERRACC REAL Accumulated reverse reactive energy value
MAXPAFD REAL Maximum forward active power demand value for set
interval
MAXPARD REAL Maximum reverse active power demand value for set
interval
MAXPRFD REAL Maximum forward reactive power demand value for set
interval
MAXPRRD REAL Maximum reactive power demand value in reverse
direction