12.1.4.4 Settings
Table 349: VMMXU Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disable / Enable
GlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base Value
groups
VLDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
VLMax 0 - 4000000 V 1 170000 Maximum value
VLRepTyp Cyclic
Dead band
Int deadband
-
- Dead band Reporting type
VLAngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Table 350: VMMXU Non group settings (advanced)
Name Values (Range) Unit Step Default Description
VLZeroDB 0 - 100000 m% 1 500 Zero point clamping
VLHiHilLim 0 - 4000000 V 1 160000 High High limit (physical value)
VLHiLim 0 - 4000000 V 1 150000 High limit (physical value)
VLLowLim 0 - 4000000 V 1 125000 Low limit (physical value)
VLowLowLim 0 - 4000000 V 1 115000 Low Low limit (physical value)
VLMin 0 - 4000000 V 1 0 Minimum value
VLLimHys 0.000 - 100.000 V 0.001 5.000 Hysteresis value in % of range and is common
for all limits
12.1.4.5 Monitored data
Table 351: VMMXU Monitored data
Name
Type Values (Range) Unit Description
V_AB REAL - kV V_AB Amplitude
VAB_ANGL REAL - deg VAB Angle
V_BC REAL - kV V_BC Amplitude
VBC_ANGL REAL - deg VBC Angle
V_CA REAL - kV V_CA Amplitude
VCA_ANGL REAL - deg VCA Angle