Table 16: GRP1_LED1 Input signals
Name Type Default Description
HM1L01R BOOLEAN 0 Red indication of LED1, local HMI alarm group 1
HM1L01Y BOOLEAN 0 Yellow indication of LED1, local HMI alarm group 1
HM1L01G BOOLEAN 0 Green indication of LED1, local HMI alarm group 1
Table 17: LEDGEN Output signals
Name Type Description
NEWIND BOOLEAN New indication signal if any LED indication input is set
ACK BOOLEAN A pulse is provided when the LEDs are acknowledged
5.3.4 Settings
Table 18: LEDGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
tRestart 0.0 - 100.0 s 0.1 0.0 Defines the disturbance length
tMax 0.0 - 100.0 s 0.1 0.0 Maximum time for the definition of a
disturbance
Table 19: GRP1_LED1 Non group settings (basic)
Name
Values (Range) Unit Step Default Description
SequenceType Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
-
- Follow-S Sequence type for LED 1, local HMI alarm
group 1
LabelOff 0 - 18 - 1 G1L01_OFF Label string shown when LED 1, alarm group 1
is off
LabelRed 0 - 18 - 1 G1L01_RED Label string shown when LED 1, alarm group 1
is red
LabelYellow 0 - 18 - 1 G1L01_YELLOW Label string shown when LED 1, alarm group 1
is yellow
LabelGreen 0 - 18 - 1 G1L01_GREEN Label string shown when LED 1, alarm group 1
is green
Section 5 1MRK 511 287-UUS A
Local Human-Machine-Interface LHMI
64
Technical manual