Each binary input has an oscillation count parameter OscillationCountx and an oscillation
time parameter OscillationTimex, where x is the number of the binary input of the module
in question.
4.1.3 Settings
4.1.3.1 Setting parameters for binary input modules
Table 8: BIO_9BI Non group settings (basic)
Name Values (Range) Unit Step Default Description
BatteryVoltage 24 - 250 V 1 110 Station battery voltage
Table 9: BIO_9BI Non group settings (advanced)
Name Values (Range) Unit Step Default Description
Threshold1 6 - 900 %VB 1 65 Threshold in percentage of station battery
voltage for input 1
DebounceTime1 0.000 - 0.100 s 0.001 0.005 Debounce time for input 1
OscillationCount1 0 - 255 - 1 0 Oscillation count for input 1
OscillationTime1 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 1
Threshold2 6 - 900 %VB 1 65 Threshold in percentage of station battery
voltage for input 2
DebounceTime2 0.000 - 0.100 s 0.001 0.005 Debounce time for input 2
OscillationCount2 0 - 255 - 1 0 Oscillation count for input 2
OscillationTime2 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 2
Threshold3 6 - 900 %VB 1 65 Threshold in percentage of station battery
voltage for input 3
DebounceTime3 0.000 - 0.100 s 0.001 0.005 Debounce time for input 3
OscillationCount3 0 - 255 - 1 0 Oscillation count for input 3
OscillationTime3 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 3
Threshold4 6 - 900 %VB 1 65 Threshold in percentage of station battery
voltage for input 4
DebounceTime4 0.000 - 0.100 s 0.001 0.005 Debounce time for input 4
OscillationCount4 0 - 255 - 1 0 Oscillation count for input 4
OscillationTime4 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 4
Threshold5 6 - 900 %VB 1 65 Threshold in percentage of station battery
voltage for input 5
DebounceTime5 0.000 - 0.100 s 0.001 0.005 Debounce time for input 5
OscillationCount5 0 - 255 - 1 0 Oscillation count for input 5
OscillationTime5 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 5