Table 206: A1A2_DC (3) Output signals
Name Type Description
089OPREL BOOLEAN Opening of 089 is allowed
089OPITL BOOLEAN Opening of 089 is not allowed
089CLREL BOOLEAN Closing of 089 is allowed
089CLITL BOOLEAN Closing of 089 is not allowed
DCOPTR BOOLEAN The bus section disconnector is in open position
DCCLTR BOOLEAN The bus section disconnector is in closed position
VPDCTR BOOLEAN Switch status of 089 is valid (open or closed)
10.4.5.6 Settings
The function does not have any settings available in Local HMI or Protection and Control
IED Manager (PCM600).
10.4.6 Interlocking for bus-coupler bay ABC_BC (3)
10.4.6.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for bus-coupler bay ABC_BC - 3
10.4.6.2 Functionality
The interlocking for bus-coupler bay (ABC_BC, 3) function is used for a bus-coupler bay
connected to a double busbar arrangement according to figure 137. The function can also
be used for a single busbar arrangement with transfer busbar or double busbar
arrangement without transfer busbar.