Name Type Description
V1RANG INTEGER V1 Magnitude range
V1ANGL REAL U1 Angle
V2 REAL U2 Amplitude
V2RANG INTEGER V2 Magnitude range
V2ANGL REAL U2 Angle
12.1.6.4 Settings
Table 359: VMSQI Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Disable/Enable Operation
3V0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
3V0Min 0 - 2000000 V 1 0 Minimum value
3V0Max 0 - 2000000 V 1 318000 Maximum value
3V0RepTyp Cyclic
Dead band
Int deadband
-
- Dead band Reporting type
3V0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is common
for all limits
3V0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
V1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
V1Min 0 - 2000000 V 1 0 Minimum value
V1Max 0 - 2000000 V 1 106000 Maximum value
V1RepTyp Cyclic
Dead band
Int deadband
-
- Dead band Reporting type
V1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
V2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
V2Min 0 - 2000000 V 1 0 Minimum value
V2Max 0 - 2000000 V 1 106000 Maximum value
V2RepTyp Cyclic
Dead band
Int deadband
-
- Dead band Reporting type
V2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is common
for all limits
V2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
1MRK 511 287-UUS A Section 12
Monitoring
435
Technical manual