EasyManua.ls Logo

ABB REC650 ANSI - Operation Principle; Monitored Data

ABB REC650 ANSI
700 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 33: OC4PTOC (51_67) Group settings (advanced)
Name Values (Range) Unit Step Default Description
HarmRestrain Disabled
Enabled
- - Disabled Enable block from harmonic restrain
2ndHarmStab 5 - 100 %IFund 1 20 Pickup of second harm restraint in % of
Fundamental
HarmRestrain1 Disabled
Enabled
- - Disabled Enable block of step 1 from harmonic restrain
HarmRestrain2 Disabled
Enabled
- - Disabled Enable block of step 2 from harmonic restrain
HarmRestrain3 Disabled
Enabled
- - Disabled Enable block of step3 from harmonic restrain
HarmRestrain4 Disabled
Enabled
- - Disabled Enable block of step 4 from harmonic restrain
Table 34: OC4PTOC (51_67) Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base Value
groups
MeasType DFT
RMS
- - DFT Selection between DFT and RMS
measurement
6.2.6 Monitored data
Table 35: OC4PTOC (51_67) Monitored data
Name
Type Values (Range) Unit Description
DIRL1 INTEGER 1=Forward
2=Reverse
0=No direction
-
Direction for phase A
DIRL2 INTEGER 1=Forward
2=Reverse
0=No direction
-
Direction for phase B
DIRL3 INTEGER 1=Forward
2=Reverse
0=No direction
-
Direction for phase C
IL1 REAL - A Current in phase A
IL2 REAL - A Current in phase B
IL3 REAL - A Current in phase C
6.2.7 Operation principle
The protection design can be divided in four parts:
1MRK 511 287-UUS A Section 6
Current protection
89
Technical manual

Table of Contents