The function IEC60870-5-103 serial communication for RS485, RS485103, is used to
configure the communication parameters for the RS485 serial communication interface.
14.9.2 Settings
Table 480: OPTICAL103 Non group settings (basic)
Name Values (Range) Unit Step Default Description
SlaveAddress 1 - 255 - 1 1 Slave address
BaudRate 9600 Bd
19200 Bd
- - 9600 Bd Baudrate on serial line
RevPolarity Disabled
Enabled
- - Enabled Invert polarity
CycMeasRepTime 1.0 - 1800.0 s 0.1 5.0 Cyclic reporting time of measurments
MasterTimeDomain UTC
Local
Local with DST
-
- UTC Master time domain
TimeSyncMode IEDTime
LinMastTime
IEDTimeSkew
-
- IEDTime Time synchronization mode
EvalTimeAccuracy Disabled
5ms
10ms
20ms
40ms
-
- 5ms Evaluate time accuracy for invalid time
EventRepMode SeqOfEvent
HiPriSpont
- - SeqOfEvent Event reporting mode
Table 481: RS485103 Non group settings (basic)
Name
Values (Range) Unit Step Default Description
SlaveAddress 1 - 255 - 1 1 Slave address
BaudRate 9600 Bd
19200 Bd
- - 9600 Bd Baudrate on serial line
CycMeasRepTime 1.0 - 1800.0 s 0.1 5.0 Cyclic reporting time of measurments
MasterTimeDomain UTC
Local
Local with DST
-
- UTC Master time domain
TimeSyncMode IEDTime
LinMastTime
IEDTimeSkew
-
- IEDTime Time synchronization mode
EvalTimeAccuracy Disabled
5ms
10ms
20ms
40ms
-
- 5ms Evaluate time accuracy for invalid time
EventRepMode SeqOfEvent
HiPriSpont
- - SeqOfEvent Event reporting mode
1MRK 511 287-UUS A Section 14
Station communication
577
Technical manual