10.10.3 Signals
Table 242: I103CMD Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of commands
Table 243: I103CMD Output signals
Name Type Description
16-AR BOOLEAN Information number 16 disable/enable autorecloser
17-DIFF BOOLEAN Information number 17, block of differential protection
18-PROT BOOLEAN Information number 18, block of protection
10.10.4 Settings
Table 244: I103CMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
10.11 IED commands for IEC 60870-5-103 I103IEDCMD
10.11.1 Functionality
I103IEDCMD is a command block in control direction with defined IED functions. All
outputs are pulsed and they are NOT stored. Pulse length is fixed to 400ms.
10.11.2 Function block
IEC10000283-1-en.vsd
I103IEDCMD
BLOCK 19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
IEC10000283 V1 EN
Figure 159: I103IEDCMD function block
1MRK 511 287-UUS A Section 10
Control
359
Technical manual