Table 232: VSGGIO Output signals
Name Type Description
BLOCKED BOOLEAN The function is active but the functionality is blocked
POSITION INTEGER Position indication, integer
POS1 BOOLEAN Position 1 indication, logical signal
POS2 BOOLEAN Position 2 indication, logical signal
CMDPOS12 BOOLEAN Execute command from position 1 to position 2
CMDPOS21 BOOLEAN Execute command from position 2 to position 1
10.6.5 Settings
Table 233: VSGGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Disable/Enable Operation
CtlModel Dir Norm
SBO Enh
- - Dir Norm Specifies the type for control model according
to IEC 61850
Mode Steady
Pulsed
- - Pulsed Operation mode
tSelect 0.000 - 60.000 s 0.001 30.000 Max time between select and execute signals
tPulse 0.000 - 60.000 s 0.001 0.200 Command pulse lenght
10.6.6 Operation principle
Selector mini switch (VSGGIO) function can be used for double purpose, in the same way
as switch controller (SCSWI) functions are used:
for indication on the single line diagram (SLD). Position is received through the
IPOS1 and IPOS2 inputs and distributed in the configuration through the POS1 and
POS2 outputs, or to IEC 61850 through reporting, or GOOSE.
for commands that are received via the local HMI or IEC 61850 and distributed in the
configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command from
the local HMI when the SLD is displayed and the object is chosen.
The output CMDPOS21 is set when the function receives an OPEN command from
the local HMI when the SLD is displayed and the object is chosen.
Section 10 1MRK 511 287-UUS A
Control
350
Technical manual