11.1.4 Signals
Table 256: SMPPTRC (94) Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of function
TRINP_3P BOOLEAN 0 Trip all phases
SETLKOUT BOOLEAN 0 Input for setting the circuit breaker lockout function
RSTLKOUT BOOLEAN 0 Input for resetting the circuit breaker lockout function
Table 257: SMPPTRC (94) Output signals
Name Type Description
TRIP BOOLEAN Common trip signal
CLLKOUT BOOLEAN Circuit breaker lockout output (set until reset)
11.1.5 Settings
Table 258: SMPPTRC (94) Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Enabled Disable/Enable Operation
tTripMin 0.000 - 60.000 s 0.001 0.150 Minimum duration of trip output signal
Table 259: SMPPTRC (94) Group settings (advanced)
Name
Values (Range) Unit Step Default Description
TripLockout Disabled
Enabled
- - Disabled On: Activate output (CLLKOUT) and trip latch,
Off: Only output
AutoLock Disabled
Enabled
- - Disabled On: Lockout from input (SETLKOUT) and trip,
Off: Only input
11.1.6 Operation principle
The duration of a trip output signal from tripping logic common 3-phase output
SMPPTRC (94) is settable (tTripMin). The pulse length should be long enough to secure
the breaker opening.
For three-pole tripping logic common 3-phase output, SMPPTRC (94) has a single input
(TRINP_3P) through which all trip output signals from the protection functions within the
IED, or from external protection functions via one or more of the IEDs binary inputs, are
Section 11 1MRK 511 287-UUS A
Logic
366
Technical manual