12.9.6 Technical data
Table 395: DRPRDRE technical data
Function
Value
Buffer capacity Maximum number of analog inputs 40
Maximum number of binary inputs 96
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time and maximum number of
channels, typical value)
340 seconds (100
recordings) at 50 Hz
280 seconds (80
recordings) at 60 Hz
12.10 IEC 61850 generic communication I/O functions
SPGGIO
12.10.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 61850 generic communication I/O
functions
SPGGIO - -
12.10.2 Functionality
IEC61850 generic communication I/O functions SPGGIO is used to send one single
logical signal to other systems or equipment in the substation.
12.10.3 Function block
SPGGIO
BLOCK
^IN
IEC09000237_en_1.vsd
IEC09000237 V1 EN
Figure 220: SPGGIO function block