17.4 Binary inputs
Table 554: Binary inputs
Description
Value
Operating range Maximum input voltage 300 V DC
Rated voltage 24...250 V DC
Current drain 1.6...1.8 mA
Power consumption/input <0.38 W
Threshold voltage 15...221 V DC (parametrizable in the range in steps of
1% of the rated voltage)
17.5 Signal outputs
Table 555: Signal output and IRF output
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 10 A
Make and carry 0.5 s 30 A
Breaking capacity when the control-circuit time
constant L/R<40 ms, at V< 48/110/220 V DC
≤0.5 A/≤0.1 A/≤0.04 A
17.6 Power outputs
Table 556: Power output relays without TCM function
Description
Value
Rated voltage 250 V AC/DC
Continuous contact carry 8 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit time
constant L/R<40 ms, at V< 48/110/220 V DC
≤1 A/≤0.3 A/≤0.1 A
1MRK 511 287-UUS A Section 17
Technical data
647
Technical manual

Table of Contents