14.8.2 Functionality
GOOSESPRCV is used to receive a single point value using IEC61850 protocol via
GOOSE.
14.8.3 Function block
GOOSESPRCV
BLOCK ^SPOUT
DATAVALID
COMMVALID
TEST
IEC10000248-1-en.vsd
IEC10000248 V1 EN
Figure 259: GOOSESPRCV function block
14.8.4 Signals
Table 477: GOOSESPRCV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
Table 478: GOOSESPRCV Output signals
Name
Type Description
SPOUT BOOLEAN Single point output
DATAVALID BOOLEAN Data valid for single point output
COMMVALID BOOLEAN Communication valid for single point output
TEST BOOLEAN Test output
14.8.5 Settings
Table 479: GOOSESPRCV Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Off/On
14.8.6 Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
1MRK 511 287-UUS A Section 14
Station communication
575
Technical manual