10.11.3 Signals
Table 245: I103IEDCMD Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of commands
Table 246: I103IEDCMD Output signals
Name Type Description
19-LEDRS BOOLEAN Information number 19, reset LEDs
23-GRP1 BOOLEAN Information number 23, activate setting group 1
24-GRP2 BOOLEAN Information number 24, activate setting group 2
25-GRP3 BOOLEAN Information number 25, activate setting group 3
26-GRP4 BOOLEAN Information number 26, activate setting group 4
10.11.4 Settings
Table 247: I103IEDCMD Non group settings (basic)
Name
Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 255 Function type (1-255)
10.12 Function commands user defined for IEC 60870-5-103
I103USRCMD
10.12.1 Functionality
I103USRCMD is a command block in control direction with user defined output signals.
These function blocks include the FunctionType parameter for each block in the private
range, and the Information number parameter for each output signal.