Name Values (Range) Unit Step Default Description
InfNo_2 1 - 255 - 1 2 Information number for output 2 (1-255)
InfNo_3 1 - 255 - 1 3 Information number for output 3 (1-255)
InfNo_4 1 - 255 - 1 4 Information number for output 4 (1-255)
InfNo_5 1 - 255 - 1 5 Information number for output 5 (1-255)
InfNo_6 1 - 255 - 1 6 Information number for output 6 (1-255)
InfNo_7 1 - 255 - 1 7 Information number for output 7 (1-255)
InfNo_8 1 - 255 - 1 8 Information number for output 8 (1-255)
10.13 Function commands generic for IEC 60870-5-103
I103GENCMD
10.13.1 Functionality
I103GENCMD is used for transmitting generic commands over IEC 60870-5-103. The
function has two outputs signals CMD_OFF and CMD_ON that can be used to implement
double-point command schemes.
The I103GENCMD component can be configured as either 2 pulsed ON/OFF or 2 steady
ON/OFF outputs. The ON output is pulsed with a command with value 2, while the OFF
output is pulsed with a command value 1. If in steady mode is ON asserted and OFF
deasserted with command 2 and vice versa with command 1. The I103GENCMD is
retained, and a command in steady mode will be reissued on restart.
The standard does not define the use of values 0 and 3. However, when connected to a
switching device, these values are transmitted.
10.13.2 Function block
IEC10000285-1-en.vsd
I103GENCMD
BLOCK ^CMD_OFF
^CMD_ON
IEC10000285 V1 EN
Figure 161: I103GENCMD function block
Section 10 1MRK 511 287-UUS A
Control
362
Technical manual