Name Type Default Description
1189G_OP BOOLEAN 0 Grounding switch 1189G on busbar WA1 is in open
position
1189G_CL BOOLEAN 0 Grounding switch 1189G on busbar WA1 is in closed
position
2189G_OP BOOLEAN 0 Grounding switch 2189G on busbar WA2 is in open
position
2189G_CL BOOLEAN 0 Grounding switch 2189G on busbar WA2 is in closed
position
7189G_OP BOOLEAN 0 Grounding switch 7189G on busbar WA7 is in open
position
7189G_CL BOOLEAN 0 Grounding switch 7189G on busbar WA7 is in closed
position
BB7_D_OP BOOLEAN 0 Disconnectors on busbar WA7 except in the own bay
are open
BC_12_CL BOOLEAN 0 A bus coupler connection exists between busbar WA1
and WA2
BC_17_OP BOOLEAN 0 No bus coupler connection exists between busbar WA1
and WA7
BC_17_CL BOOLEAN 0 A bus coupler connection exists between busbar WA1
and WA7
BC_27_OP BOOLEAN 0 No bus coupler connection exists between busbar WA2
and WA7
BC_27_CL BOOLEAN 0 A bus coupler connection exists between busbar WA2
and WA7
VOLT_OFF BOOLEAN 0 There is no voltage on the line and not VT (fuse) failure
VOLT_ON BOOLEAN 0 There is voltage on the line or there is a VT (fuse) failure
VP_BB7_D BOOLEAN 0 Switch status of the disconnectors on busbar WA7 are
valid
VP_BC_12 BOOLEAN 0 Status of bus coupler apparatuses between bus1 and
bus 2 are valid.
VP_BC_17 BOOLEAN 0 Status of the bus coupler apparatuses between Bus1
and Bus7 are valid
VP_BC_27 BOOLEAN 0 Status of the bus coupler apparatus between Bus2 and
Bus7 are valid
EXDU_89G BOOLEAN 0 No transmission error from any bay containing
grounding switches
EXDU_BPB BOOLEAN 0 No transmission error from any bay with disconnectors
on Bus7
EXDU_BC BOOLEAN 0 No transmission error from any bus coupler bay
989_EX1 BOOLEAN 0 External condition for apparatus 989
989_EX2 BOOLEAN 0 External condition for apparatus 989
189_EX1 BOOLEAN 0 External condition for apparatus 189
189_EX2 BOOLEAN 0 External condition for apparatus 189