The “Y” side currents stay untouched, while the “d” side currents are compensated
to match the currents actually flowing in the windings.
In this example there is no neutral current on either side of the transformer
(assuming there are no earthing transformers installed). In the previous example,
the matching is done differently to have the winding 1 neutral current compensated
at the same time.
Table 330: LNPLDF vector group matching
Vector group of the
transformer
Winding 1 type Winding 2 type Phase shift Zero sequence
current elimination
Yy0 Y y 0 Not needed
YNy0 YN y 0 HV side
YNyn0 YN yn 0 HV & LV side
Yyn0 Y yn 0 LV side
Yy2 Y y 2 Not needed
YNy2 YN y 2 (Automatic)
YNyn2 YN yn 2 (Automatic)
Yyn2 Y yn 2 (Automatic)
Yy4 Y y 4 Not needed
YNy4 YN y 4 (Automatic)
YNyn4 YN yn 4 (Automatic)
Yyn4 Y yn 4 (Automatic)
Yy6 Y y 6 Not needed
YNy6 YN y 6 HV side
YNyn6 YN yn 6 HV & LV side
Yyn6 Y yn 6 LV side
Yy8 Y y 8 Not needed
YNy8 YN y 8 (Automatic)
YNyn8 YN yn 8 (Automatic)
Yyn8 Y yn 8 (Automatic)