Vector group of the
transformer
Winding 1 type Winding 2 type Phase shift Zero sequence
current elimination
Yy10 Y y 10 Not needed
YNy10 YN y 10 (Automatic)
YNyn10 YN yn 10 (Automatic)
Yyn10 Y yn 10 (Automatic)
Yd1 Y d 1 Not needed
YNd1 YN d 1 (Automatic)
Yd5 Y d 5 Not needed
YNd5 YN d 5 (Automatic)
Yd7 Y d 7 Not needed
YNd7 YN d 7 (Automatic)
Yd11 Y d 11 Not needed
YNd11 YN d 11 (Automatic
Dd0 D d 0 Not needed
Dd2 D d 2 Not needed
Dd4 D d 4 Not needed
Dd6 D d 6 Not needed
Dd8 D d 8 Not needed
Dd10 D d 10 Not needed
Dy1 D y 1 Not needed
Dyn1 D yn 1 (Automatic)
Dy5 D y 5 Not needed
Dyn5 D yn 5 (Automatic)
Dy7 D y 7 Not needed
Dyn7 D yn 7 (Automatic)
Dy11 D y 11 Not needed
Dyn11 D yn 11 (Automatic)
Yz1 Y z 1 Not needed
YNz1 YN z 1 (Automatic)
YNzn1 YN zn 1 LV side
Yzn1 Y zn 1 (Automatic)
Yz5 Y z 5 Not needed
YNz5 YN z 5 (Automatic)
YNzn5 YN zn 5 LV side
Yzn5 Y zn 5 (Automatic)
Yz7 Y z 7 Not needed
YNz7 YN z 7 (Automatic)
YNzn7 YN zn 7 LV side
Yzn7 Y zn 7 (Automatic)
Yz11 Y z 11 Not needed
Table continues on next page
1YHT530004D05 D Section 4
Protection functions
615 series 359
Technical Manual