Vector group of the
transformer
Winding 1 type Winding 2 type Clock number Zro A Elimination
Zzn4 Z zn Clk Num 4 Not needed
Zz6 Z z Clk Num 6 Not needed
ZNz6 ZN z Clk Num 6 HV side
ZNzn6 ZN zn Clk Num 6 HV & LV side
Zzn6 Z zn Clk Num 6 LV side
Zz8 Z z Clk Num 8 Not needed
ZNz8 ZN z Clk Num 8 Not needed
ZNzn8 ZN zn Clk Num 8 Not needed
Zzn8 Z zn Clk Num 8 Not needed
Zz10 Z z Clk Num 10 Not needed
ZNz10 ZN z Clk Num 10 Not needed
ZNzn10 ZN zn Clk Num 10 Not needed
Zzn10 Z zn Clk Num 10 Not needed
Yy0 Y y Clk Num 0 Not needed
YNy0 YN y Clk Num 0 HV side
YNyn0 YN yn Clk Num 0 HV & LV side
Yyn0 Y yn Clk Num 0 LV side
Yy2 Y y Clk Num 2 Not needed
YNy2 YN y Clk Num 2 Not needed
YNyn2 YN yn Clk Num 2 Not needed
Yyn2 Y yn Clk Num 2 Not needed
Yy4 Y y Clk Num 4 Not needed
YNy4 YN y Clk Num 4 Not needed
YNyn4 YN yn Clk Num 4 Not needed
Yyn4 Y yn Clk Num 4 Not needed
Yy6 Y y Clk Num 6 Not needed
YNy6 YN y Clk Num 6 HV side
YNyn6 YN yn Clk Num 6 HV & LV side
Yyn6 Y yn Clk Num 6 LV side
Yy8 Y y Clk Num 8 Not needed
YNy8 YN y Clk Num 8 Not needed
YNyn8 YN yn Clk Num 8 Not needed
Yyn8 Y yn Clk Num 8 Not needed
Yy10 Y y Clk Num 10 Not needed
YNy10 YN y Clk Num 10 Not needed
YNyn10 YN yn Clk Num 10 Not needed
Yyn10 Y yn Clk Num 10 Not needed
Yd1 Y d Clk Num 1 Not needed
YNd1 YN d Clk Num 1 Not needed
Table continues on next page
Section 4 1YHT530004D05 D
Protection functions
406 615 series
Technical Manual

Table of Contents