Vector group of the
transformer
Winding 1 type Winding 2 type Clock number Zro A Elimination
Yd5 Y d Clk Num 5 Not needed
YNd5 YN d Clk Num 5 Not needed
Yd7 Y d Clk Num 7 Not needed
YNd7 YN d Clk Num 7 Not needed
Yd11 Y d Clk Num 11 Not needed
YNd11 YN d Clk Num 11 Not needed
Dd0 D d Clk Num 0 Not needed
Dd2 D d Clk Num 2 Not needed
Dd4 D d Clk Num 4 Not needed
Dd6 D d Clk Num 6 Not needed
Dd8 D d Clk Num 8 Not needed
Dd10 D d Clk Num 10 Not needed
Dy1 D y Clk Num 1 Not needed
Dyn1 D yn Clk Num 1 Not needed
Dy5 D y Clk Num 5 Not needed
Dyn5 D yn Clk Num 5 Not needed
Dy7 D y Clk Num 7 Not needed
Dyn7 D yn Clk Num 7 Not needed
Dy11 D y Clk Num 11 Not needed
Dyn11 D yn Clk Num 11 Not needed
Yz1 Y z Clk Num 1 Not needed
YNz1 YN z Clk Num 1 Not needed
YNzn1 YN zn Clk Num 1 LV side
Yzn1 Y zn Clk Num 1 Not needed
Yz5 Y z Clk Num 5 Not needed
YNz5 YN z Clk Num 5 Not needed
YNzn5 YN zn Clk Num 5 LV side
Yzn5 Y zn Clk Num 5 Not needed
Yz7 Y z Clk Num 7 Not needed
YNz7 YN z Clk Num 7 Not needed
YNzn7 YN zn Clk Num 7 LV side
Yzn7 Y zn Clk Num 7 Not needed
Yz11 Y z Clk Num 11 Not needed
YNz11 YN z Clk Num 11 Not needed
YNzn11 YN zn Clk Num 11 LV side
Yzn11 Y zn Clk Num 11 Not needed
Zy1 Z y Clk Num 1 Not needed
Zyn1 Z yn Clk Num 1 Not needed
ZNyn1 ZN yn Clk Num 1 HV side
Table continues on next page
1YHT530004D05 D Section 4
Protection functions
615 series 407
Technical Manual