Table 18: General system settings
Parameter Values (Range) Unit Step Default Description
Rated frequency 1=50Hz     1=50Hz Rated frequency of the network
Phase rotation 1=ABC
2=ACB
    1=ABC Phase rotation order
Blocking mode 1=Freeze timer
2=Block all
3=Block OPERATE
output
    1=Freeze timer Behaviour for function BLOCK inputs
Bay name
1)
     
REF615
2)
Bay name in system
IDMT Sat point 10...50 I/I> 1 50 Overcurrent IDMT saturation point
1) Used in the IED main menu header and as part of the disturbance recording identification
2) Depending on the product variant
Table 19: HMI settings
Parameter Values (Range) Unit Step Default Description
FB naming convention 1=IEC61850
2=IEC60617
3=IEC-ANSI
    1=IEC61850 FB naming convention used in IED
Default view 1=Measurements
2=Main menu
3=SLD
    1=Measurements LHMI default view
Backlight timeout 1...60 min 1 3 LHMI backlight timeout
Web HMI mode 1=Active read only
2=Active
3=Disabled
    3=Disabled Web HMI functionality
Web HMI timeout 1...60 min 1 3 Web HMI login timeout
SLD symbol format 1=IEC
2=ANSI
    1=IEC Single Line Diagram symbol format
Autoscroll delay 0...30 s 1 0 Autoscroll delay for Measurements view
Table 20: IEC 60870-5-103 settings
Parameter
Values (Range) Unit Step Default Description
Serial port 1 0=Not in use
1=COM 1
2=COM 2
    0=Not in use COM port for instance 1
Address 1 1...255     1 Unit address for instance 1
Start delay 1 0...20 char   4 Start frame delay in chars for instance 1
End delay 1 0...20 char   4 End frame delay in chars for instance 1
DevFunType 1 0...255     9 Device Function Type for instance 1
UsrFType 1 0...255     10 Function type for User Class 2 Frame for
instance 1
UsrInfNo 1 0...255     230 Information Number for User Class2
Frame for instance 1
Table continues on next page
Section 3 1YHT530004D05 D
Basic functions
48 615 series
Technical Manual