Section 12 – Power Requirements
12-3
Table 2: SIM Gateway Standby and Alarm Loads
Gateway Unit No. __________ (Maximum 72 Points)
A B AxB C AxC
Device Quantity
Standby
Current (mA)
Total
Standby
Current (mA)
Alarm
Current
(mA)
Total Alarm
Current
(mA)
SIM Door Contact
11
SIM PIR Motion
15
SIM Dual Motion
55
SIM Smoke Detector
35
SIM Holdup Button
11
SIM FA Pull Station
11
SIM
∗
11
Total Loads of SIM Sensors
(Total alarm load must not exceed 128mA)
Standby Alarm
Horn/Strobe
∗∗ ∗∗
Sounder 472307
10 10
Powered Sensors
Relay
Total Standby and Alarm Loads
on Gateway Trunk
Standby Alarm
SIM Gateway
150 50 5050
Total Gateway Standby and
Alarm Current
Standby Alarm
∗
SIM connected to external contact, powered sensor, self-powered sensor, output SIM, or horn/strobe
∗∗
190mA for bell mode with strobe, 260mA for horn/strobe