26 Rockwell Automation Publication 750-IN001P-EN-P - April 2017
Chapter 2 Prepare for Installation
Table 4 - PowerFlex 750-Series 400V/480V Input Drives RF Emission Compliance and
Installation Requirements
Standard and Limits
Drive Frame
Catalog Number
EN 61800-3 Category C1
EN 61000-6-3
CISPR11 Group 1 Class B
EN 61800-3 Category C2
EN 61000-6-4
CISPR11 Group 1 Class A
(Input Power ≤ 20 kVA)
EN 61800-3 Category C3
(I ≤ 100 A)
CISPR11 Group 1 Class A
(Input Power > 20 kVA)
EN 61800-3 Category C3
I > 100 A
Wall Mount Frame 1
20F11xx2P1…20F11xx015
20G11xx2P1…20G11xx015
N/A 30 m (98.4 ft) motor cable limit with
each wire looped once around an input
core.
(1)
(2)
30 m (98.4 ft) motor cable limit with
each wire looped once around an input
core.
(1)
N/A
Wall Mount Frame 2
20F11xx2P1…20F11xx022
20G11xx2P1…20G11xx022
150 m (492.1 ft) cable limit with
Schaffner FN3258-30-nn filter.
Supplementary EMC enclosure is
required to provide attenuation of
radiated emissions.
30 m (98.4 ft) motor cable limit with
input core.
(1)
150 m (492.1 ft) motor cable limit with
Schaffner FN3258-30-nn filter.
30 m (98.4 ft) motor cable limit with
input core.
(1)
150 m (492.1 ft) motor cable limit with
Schaffner FN3258-30-nn filter.
N/A
Wall Mount Frame 3
20F11xx030…20F11xx043
20G11xx030…20G11xx043
150 m (492.1 ft) cable limit with
Schaffner FN3258-55-nn filter.
Supplementary EMC enclosure is
required to provide attenuation of
radiated emissions.
30 m (98.4 ft) motor cable limit with
input core.
(1)
150 m (492.1 ft) motor cable limit with
Schaffner FN3258-55-nn filter.
30 m (98.4 ft) motor cable limit with
input core.
(1)
150 m (492.1 ft) motor cable limit with
Schaffner FN3258-55-nn filter.
N/A
Wall Mount Frame 4
20F11xx060…20F11xx072
20G11xx060…20G11xx072
150 m (492.1 ft) cable limit with
Schaffner FN3258-75-nn filter.
Supplementary EMC enclosure is
required to provide attenuation of
radiated emissions.
30 m (98.4 ft) motor cable limit with
input and output cores.
(1)
150 m (492.1 ft) motor cable limit with
Schaffner FN3258-75-nn filter.
30 m (98.4 ft) motor cable limit with
input and output cores.
(1)
150 m (492.1 ft) motor cable limit with
Schaffner FN3258-75-nn filter.
N/A
Wall Mount Frame 5
20F11xx085…20F11xx104
20G11xx085…20G11xx104
150 m (492.1 ft) cable limit with
Schaffner FN3258-130-nn filter.
Supplementary EMC enclosure is
required to provide attenuation of
radiated emissions.
30 m (98.4 ft) motor cable limit with
input and output cores.
(1)
150 m (492.1 ft) motor cable limit with
Schaffner FN3258-130-nn filter.
30 m (98.4 ft) motor cable limit with
input and output cores.
(1)
150 m (492.1 ft) motor cable limit with
Schaffner FN3258-130-nn filter.
30 m (98.4 ft) motor cable limit with
input and output cores.
(1)
150 m (492.1 ft) motor cable limit with
Schaffner FN3258-130-nn filter.
Wall Mount Frame 6
20F11xx140…20F11xx260
20G11xx140…20G11xx260
150 m (492.1 ft) cable limit with
22-RFD323 filter.
Supplementary EMC enclosure is
required to provide attenuation of
radiated emissions.
100 m (328.1 ft) motor cable limit with
Schaffner FN3359-320-nn filter.
150 m (492.1 ft) motor cable limit with
22-RFD323 filter.
Supplementary EMC enclosure is
required to provide attenuation of
radiated emissions.
30 m (98.4 ft) motor cable limit with no
filter.
(3)
100 m (328.1 ft) motor cable limit with
Schaffner FN3359-320-nn filter.
150 m (492.1 ft) motor cable limit with
22-RFD323 filter.
30 m (98.4 ft) motor cable limit with no
filter.
(3)
100 m (328.1 ft) motor cable limit with
Schaffner FN3359-320-nn filter.
150 m (492.1 ft) motor cable limit with
22-RFD323 filter.
Wall Mount Frame 7
20F11xx302…20F11xx477
20G11xx302…20G11xx477
150 m (492.1 ft) cable limit with
22-RFD480 filter.
Supplementary EMC enclosure is
required to provide attenuation of
radiated emissions.
150 m (492.1 ft) motor cable limit with
Schaffner FN3359-600-nn filter.
150 m (492.1 ft) motor cable limit with
22-RFD480 filter.
Supplementary EMC enclosure is
required to provide attenuation of
radiated emissions.
30 m (98.4 ft) motor cable limit with no
filter.
(3)
150 m (492.1 ft) motor cable limit with
Schaffner FN3359-600-nn filter.
150 m (492.1 ft) motor cable limit with
22-RFD480 filter.
30 m (98.4 ft) motor cable limit with no
filter.
(3)
150 m (492.1 ft) motor cable limit with
Schaffner FN3359-600-nn filter.
150 m (492.1 ft) motor cable limit with
22-RFD480 filter.
Floor Mount Frame 8 – AC Input
20G1Axx460…20G1Axx770
21G1Axx460…21G1Axx770
Compliance possible with
supplementary mitigation
(consult factory)
Compliance possible with
supplementary mitigation
(consult factory)
30 m (98.4 ft) motor cable limit
(3)
with
output core.
(4)
30 m (98.4 ft) motor cable limit
(3)
with
output core.
(4)
Floor Mount Frame 9 – AC Input
20G11xx910…20G11xx1K5
21G11xx910…21G11xx1K5
Compliance possible with
supplementary mitigation
(consult factory)
Compliance possible with
supplementary mitigation
(consult factory)
30 m (98.4 ft) motor cable limit
(3)
with
output core
(4)
and input core.
30 m (98.4 ft) motor cable limit
(3)
with
output core
(4)
and input core.
Floor Mount Frame 10 – AC
Input
20G11xx1K6…20G11xx2K1
21G11xx1K6…21G11xx2K1
Compliance possible with
supplementary mitigation
(consult factory)
Compliance possible with
supplementary mitigation
(consult factory)
30 m (98.4 ft) motor cable limit
(3)
with
output core
(4)
and input core. With door
shielding kit installed.
(5)
30 m (98.4 ft) motor cable limit
(3)
with
output core
(4)
and input core. With door
shielding kit installed.
(5)
Floor Mount Frames 8…9 –
Common DC Input
20G14xx460…20G14xx1K5
21G14xx460…21G14xx1K5
Compliance possible with
supplementary mitigation
(consult factory)
Compliance possible with
supplementary mitigation
(consult factory)
30 m (98.4 ft) motor cable limit
(3)
with
output core
(4)
and input core.
(6)
30 m (98.4 ft) motor cable limit
(3)
with
output core
(4)
and input core.
(6)
Floor Mount Frame 10 –
Common DC Input
20G14xx1K6…20G14xx2K1
21G14xx1K6…21G14xx2K1
Compliance possible with
supplementary mitigation
(consult factory)
Compliance possible with
supplementary mitigation
(consult factory)
30 m (98.4 ft) motor cable limit
(3)
with
output core
(4)
and input core.
(6)
With
door shielding kit installed.
(5)
30 m (98.4 ft) motor cable limit
(3)
with
output core
(4)
and input core. With door
shielding kit installed.
(5)
More Stringent Limits Less Stringent Limits
(1) Rating-specific EMC cores are part of EMC kit numbers 20-750-EMC1-nn and 20-750-EMC2-nn.
(2) To meet the C2 rating with a Dual Encoder module installed, Frame 1 drives must be installed in a supplementary EMC enclosure to attenuate radiated emissions.
(3) Intended to be powered from an industrial power network that is supplied by a dedicated power transformer or generator and not from LV power lines that supply other customers.
(4) EMC kit number 20-750-EMCCM1-F8. Kit contains one core. Each drive assembly requires one EMC kit. Order one kit for a Frame 8 drive, two kits for a Frame 9 drive, three kits for a Frame 10 drive.
(5) Door-shielding kit number 20-750-EMCDK1-F10. Kit contains shield brackets for three doors.
(6) EMC kit number 20-750-CBPEMCCM1-F8. Kit contains one core. Each drive assembly requires one EMC kit. Order one kit for a Frame 8 drive, two kits for a Frame 9 drive, three kits for a Frame 10 drive.