User Manual    AMETEK Programmable Power 
RS Series    92 
4.2.11  UTILITY Menus 
   
Figure 4-20: UTILITY Menus 
The UTILITY menus provide access to less frequently used setup items. There is no connection 
between the various entries in the UTILITY menu other than there is no other logical place to put 
them. The following entries can be found in the UTILITY menu: 
Entry  Description   
UTILITY 1 
GPIB/RS232 SETUP  This entry provides access to the setup parameters for either 
the IEEE-488, RS232, USB or LAN interface. All parameters 
are saved in non-volatile memory so there is rarely a need to 
change these values. 
VOLT/CURR CONTROL  The voltage and current control menu can be used to select the 
current limit method, the voltage sense source. 
  The standard available voltage range pairs are 150 Vac and 
300 Vac in AC mode or 200 Vdc and 400 Vdc in DC mode. 
  The two current limit choices are Constant Voltage and 
Constant Current.  Constant Voltage mode will maintain the set 
voltage at the output until the load current exceeds the current 
limit setting at which time the voltage will be dropped to zero.  
This effectively shuts off the AC source output in case of an 
overload condition.  This mode has user programmable trip 
delay, which is located in the same menu. 
  Constant Current mode will maintain the load current at the 
maximum level set by the current limit value, even if the 
maximum power level is exceeded.  This is done by reducing 
the voltage as needed.  As such, the voltage will be reduced 
from the set level down to zero depending on the load 
requirement.  This mode is useful for starting up motor or 
capacitor loads that may require a high inrush current.  This 
mode also has a user programmable trip delay. 
  Voltage sensing for regulation and measurement can be 
selected for internal or external.  External voltage sensing can 
compensate for voltage drops caused by load cable impedance.  
To achieve the best output regulation select external sense and 
connect the voltage sense wires at the load. 
INITIAL SETUP  The initial setup menu can be used to determine the AC source 
settings at power up. CAUTION: The initial setup can be used 
to power up the AC source with the output on and a high 
voltage present at the output. For normal situations, this is not 
recommended due to the potential danger to operators. It is 
recommended that the initial voltage be set low and/or the 
output relay be programmed to OFF for most situations.