DL205 User Manual, 4th Edition, Rev. D
4-37
Chapter 4: System Design and Configuration
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
The following examples show how to generate the Modbus address and data type for hosts which require
this format.
Example 1: V2100
Find the Modbus address for User
V location V2100.
1. Find V memory in the table.
2. Convert V2100 into decimal (1089).
3. Use the Modbus data type from the table.
Example 4: C54
Find the Modbus address for Control
Relay C54.
1. Find Control Relays in the table.
2. Convert C54 into decimal (44).
3. Add the starting address for the
range (3073).
4. Use the Modbus data type from the
table.
Outputs (Y) 320 Y0 – Y477 2049 – 2367 Coil
Control Relays (CR) 256 C0 – C377 3072 - 3551 Coil
Timer Current Values (V) 128 V0 – V177 0 – 128 Input Register
Counter Current Values (V) 128 V1000 – V1177 512 – 639 Input Register
Outputs (Y) 320 Y0 – Y477 2048 - 2367 Coil
Control Relays (C) 256 C0 – C377 3073 – 3551 Coil
PLC Address (Dec.) + Data Type
V2100 = 1088 decimal
1088 + Hold. Reg. =
PLC Addr. (Dec) + Start Addr.
+ Data Type
Y20 = 16 decimal
16 + 2049 + Coil =
PLC Address (Dec.) + Data Type
T10 = 8 decimal
8 + Input Reg. =
PLC Addr. (Dec) + Start Addr. +Data Type
C54 = 44 decimal
44 + 3073 + Coil =
Coil 2065
Holding Reg. 1089
Input Reg. 9
Coil 3117
Timer Current Values (V) 128 V0 - V177 0 - 127 Input Register
Counter Current Values (V) 128 V1000 - V1177 512 - 639 Input Register
V Memory, user data (V) 1024 V2000 - -V3777 1024 - 2047 Holding Register
Example 3: T10 Current Value
Find the Modbus address to obtain the current
value from Timer T10.
1. Find Timer Current Values in the table.
2. Convert T10 into decimal (8).
3. Use the Modbus data type from the table.
Example 2: Y20
Find the Modbus address for output Y20.
1. Find Y outputs in the table.
2. Convert Y20 into decimal (16).
3. Add the starting address for the range (2049).
4. Use the Modbus data type from the table.

Table of Contents

Other manuals for AutomationDirect DL205

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AutomationDirect DL205 and is the answer not in the manual?

AutomationDirect DL205 Specifications

General IconGeneral
BrandAutomationDirect
ModelDL205
CategoryController
LanguageEnglish

Related product manuals