DL205 User Manual, 4th Edition, Rev. D
3-5
Chapter 3: CPU Specifications and Operations
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Specification AC Powered Bases 24 VDC Powered Bases 125 VDC Powered Bases
Part Numbers
D2–03B–1
D2–04B–1
D2–06B–1
D2–09B–1
D2–03BDC1–1
D2–04BDC1–1
D2–06BDC1–1
D2–09BDC1–1
D2–06BDC2–1
D2–09BDC2–1
Input Voltage Range
100–240 VAC +10% –15%
10.2–28.8 VDC (24VDC)
with less than 10% ripple
104–240 VDC +10% –15%
Maximum Inrush Current
30A 10A 20A
Maximum Power
80VA 25W 30W
Voltage Withstand (dielectric)
1 minute @ 1500VAC between primary, secondary, field ground, and run relay
Insulation Resistance
> 10Mq at 500VDC
Auxiliary 24 VDC Output
20–28 VDC, less than 1V p-p
300mA max.
None
20–28 VDC, less than 1V p-p
300mA max.
Fusing (internal to base power
supply)
Non–replaceable 2A @ 250V
slow blow fuse
Non–replaceable 3.15 A @
250V slow blow fuse
Non–replaceable 2A @ 250V
slow blow fuse
Feature DL230 DL240 DL250–1 DL260
Number of instructions available
(see Chapter 5 for details)
92 129 240 297
Control relays
256 256 1024 2048
Special relays (system defined)
112 144 144 144
Stages in RLL
PLUS
256 512 1024 1024
Timers
64 128 256 256
Counters
64 128 128 256
Immediate I/O
Yes Yes Yes Yes
Interrupt input (hardware / timed)
Yes / No Yes / Yes Yes / Yes Yes / Yes
Subroutines
No Yes Yes Yes
Drum Timers
No No Yes Yes
Table Instructions
No No No Yes
For/Next Loops
No Yes Yes Yes
Math
Integer Integer
Integer,
Floating Point
Integer,
Floating Point,
Trigonometric
ASCII
No No Yes, OUT Yes, IN/OUT
PID Loop Control, Built In
No No Yes, 4 Loops Yes, 16 Loops
Time of Day Clock/Calendar
No Yes Yes Yes
Run Time Edits
Yes Yes Yes Yes
Supports Overrides
No Yes Yes Yes
Internal diagnostics
Yes Yes Yes Yes
Password security
Yes Yes Yes Yes
System error log
No Yes Yes Yes
User error log
No Yes Yes Yes
Battery backup
Yes (optional) Yes (optional) Yes (optional) Yes (optional)
CPU Base Electrical Specifications