DL205 User Manual, 4th Edition, Rev. D
5-33
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Immediate Instructions
Store Immediate (STRI)
The Store Immediate instruction begins a new rung or
additional branch in a rung. The status of the contact
will be the same as the status of the associated input point
at the time the instruction is executed. The image register
is not updated.
Store Not Immediate (STRNI)
The Store Not Immediate instruction begins a new rung
or additional branch in a rung. The status of the contact
will be opposite the status of the associated input point at
the time the instruction is executed. The image register is
not updated.
In the following example, when X1 is on, Y2 will energize.
In the following example, when X1 is off, Y2 will energize.
aaaX
aaaX
230
240
250-1
260
230
240
250-1
260
ENT
2
C
1
B
ENT
X1
Y2
OUT
Handheld Programmer KeystrokesDirectSOFT
STR
$
SHFT
8
I
OUT
GX
Operand Data Type DL230 Range DL240 Range DL250-1 Range DL260 Range
aaa aaa aaa aaa
Inputs X 0–177 0–477 0–777 0–1777
ENT
2
C
1
B
ENT
X1
Y2
OUT
Handheld Programmer Keystrokes
DirectSOFT
STRN
SP
SHFT
8
I
OUT
GX
DS Implied
HPP Used