EasyManua.ls Logo

AutomationDirect DL205 - D2-08 NA-1, AC Input

Default Icon
598 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DL205 User Manual, 4th Edition, Rev. D
2-33
Chapter 2: Installation, Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
D2-08NA-1, AC Input
Optical
COM
Isolator
INPUT
110VAC
V+
To LE D
Internal module circuitry
COM
C
C
0
1
2
3
4
5
6
7
Internally
connected
110VAC
0
2
4
6
8
0
10 20 30 40 50 55
AmbientTemperature (˚C/˚F)
32
50 68 86 104 122 131
C˚
F˚
Points
C
C
0
4
1
5
2
6
3
7
80-132VAC
10-20mA
D2-- 08NA-1
IN 110
D2-- 08NA-- 1
VAC
0
1
2
3
4
5
6
7
50/60Hz
Line
Derating Chart
D2-08NA-1 AC Input
Inputs per Module
8
Commons per Module
1 (2 I/O terminal points)
Input Voltage Range
80–132 VAC
Peak Voltage
132VAC
ON Voltage Level
75VAC minimum
OFF Voltage Level
20VAC maximum
AC Frequency
47–63 Hz
Input Impedance
12kq @ 60Hz
Input Current
13mA @ 100VAC, 60Hz
11mA @ 100 VAC, 50Hz
Minimum ON Current
5mA
Maximum OFF Current
2mA
Base Power Required 5VDC
50mA
OFF to ON Response
5 to 30 ms
ON to OFF Response
10 to 50 ms
Terminal Type (included)
Removable; D2-8IOCON
Status Indicator
Logic side
Weight
2.5 oz. (70g)

Table of Contents

Other manuals for AutomationDirect DL205

Related product manuals