Table 2: User Supplied Materials
ONS 15454 M6ONS 15454 M2ONS 15454User
Supplied
Material
ANSI
Bit error rate (BER) tester, DS-1
and DS-3
Bit error
rate (BER)
tester
ANSI
BNC insertion tool
BNC
insertion
tool
ANSI
• Power cable (from fuse
and alarm panel to
assembly), #8 AWG or
larger, copper
conductors, 194 degrees
Fahrenheit (90 degrees
Celsius).
• Ground cable #6 AWG
stranded
• Alarm cable pairs for all
alarm connections, #22
or #24 AWG (0.51 mm²
or 0.64 mm²), solid
tinned.
• 100-ohm shielded
building integrated
timing supply (BITS)
clock cable pair #22 or
#24 AWG (0.51 mm² or
0.64 mm²), twisted-pair
T1-type
ETSI
• Copper ground cable
13.3-mm² (#6 AWG)
stranded, specified for
up to 90 degrees Celsius
(194 degrees
Fahrenheit)
• Alarm cable pairs for all
alarm connections, 0.51
mm² or 0.64 mm² (#22
or #24 AWG),
solid-tinned
ANSI
• Power cable (from fuse
and alarm panel to
assembly), #12 AWG
or larger, copper
conductors, 194 degrees
Fahrenheit (90 degrees
Celsius).
• Ground cable #6 AWG
stranded
• Alarm cable pairs for
all alarm connections,
#22 or #24 AWG (0.51
mm² or 0.64 mm²),
solid tinned.
• 100-ohm shielded
building integrated
timing supply (BITS)
clock cable pair #22 or
#24 AWG (0.51 mm² or
0.64 mm²), twisted-pair
T1-type
ETSI
• Copper ground cable
13.3-mm² (#6 AWG)
stranded, specified for
up to 90 degrees
Celsius (194 degrees
Fahrenheit)
• Alarm cable pairs for
all alarm connections,
0.51 mm² or 0.64 mm²
(#22 or #24 AWG),
solid-tinned
ANSI
• Power cable (from fuse and
alarm panel to assembly),
#10 AWG, copper
conductors, 194 degrees
Fahrenheit (90 degrees
Celsius).
• Ground cable #6 AWG
stranded
• Alarm cable pairs for all
alarm connections, #22 or
#24 AWG (0.51 mm² or 0.64
mm²), solid tinned.
• 100-ohm shielded building
integrated timing supply
(BITS) clock cable pair #22
or #24 AWG (0.51 mm² or
0.64 mm²), twisted-pair
T1-type
• Shielded coaxial cable
terminated with SMB or
BNC connectors for DS-3
cards.
• Shielded ABAM cable
terminated with AMP Champ
connectors or unterminated
for DS1N-14 cards with #22
or #24 AWG (0.51 mm² or
0.64 mm²) ground wire
(typically about two ft [61
cm] in length)
• 6-pair #29 AWG
double-shielded cable
Cables
Cisco ONS 15454 Hardware Installation Guide
12
Preparing to Install the ONS 15454 (ANSI and ETSI), ONS 15454 M2 and ONS 15454 M6 Shelf
User Supplied Materials