108 5.6 DIII-NET Plus Adaptor Connection
intelligent Touch Controller
5.6 DIII-NET Plus Adaptor Connection
5.7 Connection for Unification Adaptor
DIII-NET Plus Adapter
CPU Alive
<< CAUTION >>
• Don't clamp these cables together with high
voltage cables. Failure to observe this
instruction would cause control error.
In order to increase the number of indoor units to be controlled, connect DIII-NET Plus adaptor using
RS232-C cable attached to the adaptor.
For details, refer to the installation manual of DIII-NET Plus adaptor.
PHONE RS-232CLINE LAN
DAIKIN
In order to perform total start and stop/situation monitoring from central supervisory board, etc.,
connect a Unification Adaptor sold separately.
As shown in the sketch below, open the controller and connect the cable from the Unification Adaptor to
CN2 connector located on the printed board on the lower case.
If you route the cable in the cable guide groove on the lower case, you can make a smart connection without
any slack of the cable.
CN2
W1 W2W3 W4
• Don't clamp these cables
together with high voltage cables. Failure to
observe this instruction would cause control error.
CN2
B1
B2
BC
<< CAUTION >>