344 2.5 <DTA103A51> Wiring Adaptor for Other Air Conditioners
Adaptor
2.5 <DTA103A51> Wiring Adaptor for Other Air Conditioners
2.5.1 Function
This kit contains an I/O interface adaptor for centralized controllers, used when there is a non-connectable air conditioner
and electrical equipment. When connected to the central control line, this adaptor enables operation/stop and display of
operation/error monitors from the optional controller.
2.5.2 Part Names and Functions
2.5.3 Installation
Securely install the adaptor with the attached installation screw.
Note:
Install the adaptor inside a control box of outer dimensions: 230W × 230D × 60H.
Supply a control box at site with outer dimensions equal to or larger than those shown below. 230W × 230D × 60H.
Type BRC1C62 DTA103A51
Group/Zone
Item
One Group Unified control for all Zone
ON/OFF Possible Possible
Temp. setting Possible Impossible
Air flow rate setting Possible Impossible
Air flow direction setting Possible Impossible
Timer setting twice a day Possible Impossible
Mode setting Possible Impossible
Filter sign reset Possible Impossible
Inspection/Test operation Possible Operation & Error display only by lamps