64 3.1 Function List
Remote Controllers
3. Functions of Remote Controllers
3.1 Function List
3.2 Example of Control by Remote Controller
Appearance
Type Wired R/C Wireless R/C Simplified R/C R/C for Hotel Use
ON/OFF Possible Possible Possible Possible
Temp. setting Possible Possible Possible Possible
Air flow rate setting Possible Possible Possible Possible
Air flow direction setting Possible Possible
Timer setting Possible Possible
Mode setting Possible Possible Possible
Filter sign reset Possible Possible
Inspection/Test operation Possible Possible
Cool/heat operation mode selection control
In the case of VRV System Inverter Series, you can
select cool/heat operation mode by indoor remote
controller for outdoor units within the same system.
Control with two remote
controllers
You can connect 2 remote
controllers, for example from
an indoor unit and the
control room, to 1 indoor
unit and control as you like
(last command priority), and
of course group control by 2
remote controllers is also
possible.
Remote control
You can extend remote
control wiring up to a
maximum of 500 m, and you
can easily centrally locate
the remote controller in one
place for indoor units
located in various places in
the room.
Combined control
A total heat exchanger unit
VRV system etc. can be
simultaneously controlled
via an indoor unit.
System expansion
Various system expansions
such as forced ON/OFF
command input from a
building control system or
key control system can be
carried out.
Group control
You can simultaneously control up to 16 indoor
units with 1 remote controller.
Outdoor unit
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Remote controller
HRV system
Remote
controller
Remote
controller
Indoor unit
Forced ON/OFF input