88 5.4 HRV <BRC301B61>
Remote Controllers
5.4 HRV <BRC301B61>
Note:
When you make the plural setting to one (or one group) indoor unit, the item 2 to 6 of the above setting procedure should
be repeated and it should be returned to the “normal mode” by the procedure of item 7 at last.
The following describes the operating procedure and settings.
1 Press the INSPECTION button for more than four seconds to enter
the local setting mode when the unit is in the normal mode.
2 Use the VENTILATION MODE, AIR FLOW RATE button to select
the desired “mode number”. (The code display will blink.)
3 To make setting for individual unit under group control (when mode
no. 27, 28 or 29 is selected), press TIMER SETTING ON / OFF
button to select the “unit No.” for which the settings are to be made.
(This process is not necessary when settings are made collectively
for the group.)
4 Press the top section of the TIMER button to select the “setting
switch No.”.
5 Press the lower section of the TIMER button to select the “setting
position No.”.
6 Press the PROGRAM / CANCEL button once to enter the settings.
(The code display will stop blinking and light up.)
7 Press the INSPECTION button to return to normal mode.
BRC301B61
HR
HR
V
UNIT No.
FRESH UP
CODE
GROUP
A
A
hr
hr
SETTING
3
3
2
4, 5
1, 7
4 5
6