234 8.1 File Name
Interface for use in LONWORKS
®
8. Precautions Regarding XIF Files
8.1 File Name
DMS_IF02.XIF
8.2 Limitations with Version 3
Daikin's XIF file is written in the Version 3 format, and the default values for configuration properties (CP) are not written
within the XIF file. Therefore, when using a LonMaker to add devices, be sure to conduct the procedures at the CP value
of "Current values in device" and not that of "Default values in the XIF file".
8.3 Unused Network Variables
The network variables listed below do exist within our XIF file, but are not explained in these specifications. These are
intended strictly for internal use and should not be used.
nvoWattmeter
nviSetTime
nvi SetNetDB
nvoSetNetDB