5.8 DIII-NET Plus Adaptor 109
intelligent Touch Controller
5.8 DIII-NET Plus Adaptor
z Use a round crimp terminal with reinforcing sleeve for safety wiring connection to this unit.
*
*
*
DAIKIN
F1 F2
F1
F2
F1 F2 F1 F2 F1 F2 F1 F2
F1 F2
Polarity : No
Pi3
3-M4
Pi2
DCS601A52
N
Standard accessory
0.75~1.25mm
2
vinyl cord or cable with up to
150m maximum.
Pi1
RS232-C
Measuring meter × 3
(Where Power Proportional
Distribution Card as option is used)
Power supply wiring 2.0mm
2
Implement the grounding in accordance with the
standards of the applicable county and region.
Earth wiring 2.0mm
2
F2
RS232C
Pi1
DCS601C51
RS232 - C
*RS232C wiring
DCS601A52
Wirings must be isolated from the power lines.
RS232 - C Cable (10m) *Standard accessory
L
F1
*DIII - NET wiring
6-M3.5
Pi2
The measuring meters to be connected must meet the requirements specified below.
1. To be a measuring meter with pulse oscillator. (pulse/kwh)
2. Pulse band of 100msec or mores
3. Measuring meter which uses semiconductor relay for pulse output and outputs pulses from non-voltage
contact1. Use a no voltage contact.
4. Use a contact which can guarantee minimum application load DC16V and 10mA.
5. Wirings must be isolated from the power lines.
6. Terminal contact size : M3.5.
DCS601A52
*Measuring meter
Earth leakage breaker
10A
Power supply
Single phase
100 - 240V
(50/60Hz)
1. Do not use multicore cables with three or more cores.
2. Use wires of sizes between 0.75mm
2
and 1.25mm
2
3. Wire length : Max 1000m
4. Do not bind the wire for DIII-NET
5. Wirings for DIII-NET must be isolated from the power lines.
6. Terminal contact size : M3.5
DIII-NET Plus Adapter
COM
Pi3
Outdoor unit
maximum of 64groups
COM
RS232C