178 2.1 System Configuration of intelligent Manager
intelligent Manager
2. System Design of intelligent Manager
2.1 System Configuration of intelligent Manager
2.2 List of Required Devices for intelligent Manager System
Device Classification Prepared by Model / Spec. Remarks
iPU Essential Daikin DAM602B51 Model with a 4-port D3 port
DAM602B52 Model with a 2-port D3 port
PC Essential Customer Pentium III 800MHz or faster
Memory 256MB or more
HD 4GB or more
PC for intelligent Manager
Windows XP Professional SP2 or later
Windows 2000 Professional SP4 or later
Up to 2 units can be installed on LAN.
Monitor Essential Customer Resolution of 800 x 600 or higher 800×600 or 1,024×768 or 1,280×1,024
HUB Essential Customer 100 Base/T Used to connect iPU and PC.
UPS Essential Customer APC SU700 or SU1000 series Supplies power to iPU, PC and HUB.
Essential Customer APC AP9610 Required to transmit a power failure signal of UPS to
iPU.
Di/Dio Op Daikin DEC101A51 (Di)
DEC102A51 (Dio)
Used to connect devices of other companies.
Ai Op Daikin DAM101A51 Used to measure outside air temperature.
Modem Op Customer Specified by service division Required for Airnet connection.
One unit is required for each intelligent Manager
system.
kWh
meter
Op Customer Pulse output: 1kWh/pulse
Pulse width: 40 - 400 msec
Required when PPD is used.
The number of units will be determined in
accordance with the design.
PLC Op Customer OMRON SYSMAC CJ1 Used to measure analog values such as
temperature, humidity, and pressure.
Op Customer CJ1W-PTS Temperature measurement terminal
Op Customer CJ1W-AD etc. ... Analog value measurement terminal
Pulse signal
I/O
DIII net
LAN (Ethernet)
HUB
UPS
Power Line
PC
iPU
Fire detection System, etc.
RS232C
Contact signal
Contact signal
DIII
Device
DeviceNet
When using measurement
function of PLC
Optional function
Modem
When using
Air Conditioning
Network Service System
Optional function
*UP to 4 units of iPU can be connected
kWh meter
(1kWh/pulse)
Optional function
When using
proportional power
ACC center
Standard configuration
System Configuration Diagram