208 1.9 Electric Wiring
Interface for Use in BACnet
®
1.9.3 Electric Wiring Connections
Everything relating with field wiring must be supplied in the field.
1. DIII-NET Wiring
1P191170C
Outdoor
unit
Outdoor
unit
Outdoor
unit
Outdoor
unit
F1
Terminal contact size : M3.5
F2
F1
F2
F1
DMS502B51
Recommended wire size 0.75~1.25mm
2
Recommended wire size 0.75~1.25mm
2
polarity : No
polarity : No
polarity : No
polarity : No
F2
Terminal contact size : M3.5
DIII – 1
DIII – 2
DIII – 3
DIII – 4
F2
DAM411B51(Option)
F1
F1 F2 F1 F2 F1 F2 F1 F2
F1 F2 F1 F2 F1 F2 F1 F2
F1 F2 F1 F2 F1 F2 F1 F2
F1 F2 F1 F2 F1 F2 F1 F2
Cautions for wiring
1. Do not use multicore cables with three or more cores
2. Use wires of sizes between 0.75mm
2
and 1.25mm
2
3. Do not bind the wire for DIII-NET
4. Wirings for DIII-NET must be isolated from the power lines
5. Wire length : Max 1000m