240 12.2 System Configuration
Interface for use in LONWORKS
®
12.2.3 Location Address Setting and Combined Use of Other Centralized Devices
- DDS, D-BIPS, Interface for BACnet Gateway and DMSII cannot be installed/used together on the same DIII-NET.
- Only one Interface for LONWORKS
®
can be installed on a DIII line.
- A Centralized Controller, intelligent Controller, ON/OFF Controller and Heat Storage Controller can be installed/used
together.
(The maximum number of groups that can be connected is 64, so there are restrictions on the number of centralized
devices that can be connected.)
- A schedule timer cannot be installed/used together.
- The combined installation/use of a Centralized Controller and intelligent Controller is recommended to allow for
independent centralized control if the LONWORKS system shuts down.
<Example>