20
Outline of D-BACS System
DIII : Fundamental policy,
Yes: Possible or Available, No: Impossible or non-existent BMS : Depending on BMS manufacturer
Central control device name
intelligent Touch
Controller
intelligent Manager III
Remote
Controller
BACnet
TM
Gate-way
LonTalk
TM
Inter-face
Central Remote
Controller
Unified ON/OFF
controller
Schedule
timer
Product name or System name iM 128 iM 256 iM 512 iM 768 iM 1024
Hardware Model Name for one system
DCS60
1C51
DCS60
1C51
DAM60
2B52
DAM60
2B51
DAM60
2B51x2
DAM60
2B51x3
DAM60
2B51x4
BRC1C62
DMS50
2B51
DMS50
2B51
DMS504B
51
DCS302
CA61
DCS302
CA61x2
DCS301
BA61
DCS301
BA61x8
DST301BA
61
DCS60
1A52
DAM41
1B51
Function Detail
System setup
TEMPERATURE LIMIT
SETTINGS
Prevention of excessive
temperature increases/deceases
in unmanned rooms ( Cooling
OFF at 4 deg. C below the max.
temp. and heating OFF at 4 deg.
C above the min. temp. in terms of
suction temp. )
Yes / 128 Gps. for
1 setting, 8
settings
Yes No No No No
HEATING
OPTIMIZATION
SETTINGS
Fan operation stop in order to
prevent temperature increases
( circulating of a small volume of
refrigerant) during the Heating
mode or thermo Off ( because
there is no Fan Off function)
Yes Yes No No No No
Control of other facilities
On/Off with using equipment of Di,
Dio unit, ADP
Yes Yes Yes Yes Yes
SLIDING
TEMPERATURE
SETTINGS
Automatic temperature setting to
minimize drastic temperature
differences with the outdoors
No Yes No No No No
POWER LIMIT
CONTROL
Providing control to limit A/C
power consumption to the set
targets
No YES*1 No No No No
ECO MODE
Within the daily interval during the
calendar based seasons, 3
groups of indoor units can be
stopped for a ratio of 10,
20,30,40%, and/or 2 outdoor units
can be lowered for the capacity
for a ratio of 40, 70%
No Yes NoNoNoNo NoNo
Energy efficiency
Shift of the set temperature by 2
degree
No YES, the same as *1 No Yes No No No
Watch DOG
An office PC can receive
telephone remote monitor of error
messages from the iM PC.
No Yes No BMS BMS No No No
Remote intelligent
Manager
An office remote PC can control
and monitor the iM monitoring PC
via public phone lines.
No Yes No BMS BMS No No No
Interlocking Yes Yes/100 links No BMS BMS No No No