2.3 Connection Method 29
Fundamental of DIII-NET
2.3.2 Bad example
Caution
Communication problems could occur.
[Bad Example 1]
Caution
As shown above, the central remote controllers should be connected to the wiring between the outdoor units, wherever
possible. (If connected to the control wiring between indoor unit and the outdoor unit, it may not be able to control the
units even on the normal circuit if the circuit connected to the central controller is out of order.)