Loading...
-
-
-
-
-
-
-
-
154.2
126
Ø5
Ø5
Ø10
328.5
308
300
82.8
e30bh488.10
Illustration 89: Control Unit Dimensions
12.4 Cable and Fuse Sizes
For cable, and fuse size information, see the following topics:
380–500 V AC:
12.4.1 Internal Cable Sizes for 380–500 V AC
12.4.2 Busbar and Terminal Dimensions for 380–500 V AC
12.4.3 Fuse Sizes for 380–500 V AC, 6-pulse
12.4.4 Fuse Sizes for 380–500 V AC, 12-pulse
525–690 V AC:
12.4.5 Internal Cable Sizes for 525–690 V AC
12.4.6 Busbar and Terminal Dimensions for 525–690 V AC
12.4.7 Fuse Sizes for 525–690 V AC, 6-pulse
12.4.8 Fuse Sizes for 525–690 V AC, 12-pulse
12.4.1 Internal Cable Sizes for 380–500 V AC
Table 34: Cable Sizes for 380–500 V AC, FR8–FR12
Enclosure size
Drive type
Temperature rating
(1)
Internal cable/phase [mm
2
]
FR8
NXP 0140 5
90 °C (194 °F)
70
70 °C (158 °F)
95
NXP 0168 5
90 °C (194 °F)
70
70 °C (158 °F)
95
NXP 0205 5
90 °C (194 °F)
95
70 °C (158 °F)
120
FR9
NXP 0261 5
90 °C (194 °F)
2*70
70 °C (158 °F)
2*95
NXP 0300 5
90 °C (194 °F)
2*70
70 °C (158 °F)
2*95
AQ351737303996en-000201 / DPD00888132 | Danfoss A/S © 2023.09