Table 38: Busbar Dimensions for 380–500 V AC, FR13–FR14
Enclosure size
Drive type
Cu busbar size
Busbars total
FR13
NXP1150
40*6 mm
6
NXP1300-1500 (6-p)
40*6 mm
9
NXP1300-1500 (12-p)
40*6 mm
12
FR14
NXP1770-2150
40*6 mm
12
12.4.3 Fuse Sizes for 380–500 V AC, 6-pulse
The aR fuses are thermally rated into switch fuse in 50 °C (122 °F) ambient temperature.
Table 39: Fuse Sizes for 380–500 V AC, FR8–FR9, 6-pulse
Enclosure size
Drive type
Fuse (gG/gL) [A]
Fuse Class Fast Acting (T/J) [A]
FR8
0140
160
175
0168
200
250
0205
250
250
FR9
0261
315
350
0300
315
400
Table 40: Fuse Sizes (Bussmann) for 380–500 V AC, FR10–FR12, 6-pulse
Enclo-
sure size
Drive
type
DIN 43620
DIN 43653 (110 mm)
Flush end contacts (met-
ric)
Fuse
[A]
Fuses
per
drive
aR fuse part
nr.
Fuse size
aR fuse part
nr.
Fuse size
aR fuse part
nr.
Fuse size
FR10
385
170M5813
DIN 2
170M5213
2TN/110
170M5463
2BKN/50
700
3
460
170M8547
3SHT
(1)
170M6216
3TN/110
170M6466
3BKN/50
1250
3
520
170M8547
3SHT
()
170M6216
3TN/110
170M6466
3BKN/50
1250
3
FR11
590
170M5813
DIN 2
170M5213
2TN/110
170M5463
2BKN/50
700
6
650
170M5813
DIN 2
170M5213
2TN/110
170M5463
2BKN/50
700
6
730
170M5813
DIN 2
170M5213
2TN/110
170M5463
2BKN/50
700
6
FR12
820
170M8547
3SHT
()
170M6216
3TN/110
170M6466
3BKN/50
1250
6
920
170M8547
3SHT
()
170M6216
3TN/110
170M6466
3BKN/50
1250
6
1030
170M8547
3SHT
()
170M6216
3TN/110
170M6466
3BKN/50
1250
6
FR12
DC-link
(2)
170M5813
DIN 2
170M5213
2TN/110
170M5463
2BKN/50
700
2
1
SHT fuses can be assembled into same size DIN fuse base
SHT fuses can be assembled into same size DIN fuse base
2
In FR12 (12-pulse drive) or in FR12 (6- or 12-pulse) with internal brake, the DC-links between units are connected together. If connected together,
there must be DC-link fuses in DC-minus and DC-plus poles between the units. (In 6-pulse drive without internal brake, DC-links between units are
separate and there is no need for fuses.)
AQ351737303996en-000201 / DPD00888134 | Danfoss A/S © 2023.09
Specifications
VACON® NXP IP00 Drive Modules
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VACON NXP IP00 and is the answer not in the manual?

Danfoss VACON NXP IP00 Specifications

General IconGeneral
BrandDanfoss
ModelVACON NXP IP00
CategoryControl Unit
LanguageEnglish

Related product manuals