Threaded end
contacts (metric)
1
In FR12 (12-pulse drive) or in FR12 (6- or 12-pulse) with internal brake, the DC-links between units are connected together. If connected together,
there must be DC-link fuses in DC-minus and DC-plus poles between the units. (In 6-pulse drive without internal brake, DC-links between units are
separate and there is no need for fuses.)
12.5 AC Chokes
Table 58: AC Chokes for 380–500 V AC
Table 59: AC Chokes for 525–690 V AC