1.
2.
3.
4.
5.
1.
2.
3.
5.5 Installation Sequence
5.5.1 Installation Sequence for FR8–FR12
Use these instructions to install the VACON
®
NXP IP00 Drive Modules.
Check the following:
Environmental requirements, see 5.1 Environmental Requirements
Cooling requirements, see 5.2 Cooling Requirements
Cabinet requirements, see 5.3 Cabinet Requirements for FR8–FR12
The dimensions of the AC drive, see 12.3.3 List of Dimension Information
Procedure
FR10–FR12: Install the AC choke, see 5.5.1.1 Mounting the AC Choke, FR10–FR12.
Install the power unit, see 5.5.1.2 Mounting the Power Unit, FR8–FR12.
If the drive was ordered with the control unit separated from the power unit, install the control unit, see 5.5.1.3 Mounting
the Control Unit, FR8–FR12.
The VACON
®
NXP FR10–FR12 drive can be delivered with the control unit either integrally mounted on the power unit or
separated from the power unit and fixed to the mounting box. The mounting box can be installed to a sidewall or the
frame of the enclosure.
Make sure that there is sufficiently free space around the AC drive for cooling, see
5.2 Cooling Requirements. Some free
space is also necessary for maintenance.
Continue to the grounding and cabling, see 6.7 Installing the Cables.
5.5.1.1 Mounting the AC Choke, FR10–FR12
This topic gives instructions on how and where to mount the AC choke in the cabinet for VACON® NXP IP00 Drive Modules, FR10–
FR12.
NOTE! VACON® NXP IP00 Drive Modules, FR8 and FR9 does not have the external AC choke.
Procedure
Mount the AC choke in the bottom part of the cabinet close to the rear wall.
In case a fuse switch is later installed, mount the AC choke somewhat to the left.
Fasten the AC choke on an assembly plate or using mounting rails.
If the cabinet is transported in horizontal position, install an upper support plate above the AC choke, and equip the sup-
port plate with air circulation holes.
Illustration 16: Mounting AC Choke
AQ351737303996en-000201 / DPD0088838 | Danfoss A/S © 2023.09
Mounting the Unit
VACON® NXP IP00 Drive Modules
Operating Guide