Enclo-
sure size
Drive type
Loadability
(1)
Motor shaft power
Low
High
690 V supply
575 V supply
Rated
continu-
ous cur-
rent I
L
(A)
(2)
Rated
overloa
d cur-
rent (A)
Rated
continu-
ous cur-
rent I
H
(A)
50 %
over-
load
current
(A)
Max
current
I
S
Low
over-
load P
(kW)
High
over-
load P
(kW)
Low
over-
load P
(kW)
High
over-
load P
(kW)
NXP0100 6
100
110
80
120
160
90
75
100
75
FR9
NXP0125 6
125
138
100
150
200
110
90
125
100
NXP0144 6
144
158
125
188
213
132
110
150
125
NXP0170 6
170
187
144
216
245
160
132
150
150
NXP0208 6
208
229
170
255
289
200
160
200
150
FR10
NXP0261 6
261
287
208
312
375
250
200
250
200
NXP0325 6
325
358
261
392
470
315
250
300
250
NXP0385 6
385
424
325
488
585
355
315
400
300
NXP0416 6
(3)
416
416
325
488
585
400
315
450
300
FR11
NXP0460 6
460
506
385
578
693
450
355
450
400
NXP0502 6
502
552
460
690
828
500
450
500
450
NXP0590 6
(3)
590
649
502
753
904
560
500
600
500
FR12
NXP0650 6
650
715
590
885
1062
630
560
650
600
NXP0750 6
750
825
650
975
1170
710
630
800
650
NXP0820 6
(3)
820
902
650
975
1170
800
630
750
650
FR13
NXP0920 6
920
1012
820
1230
1410
900
800
900
800
NXP1030 6
1030
1130
920
1380
1755
1000
900
1000
900
NXP1180 6
(3)
1180
1298
1030
1463
1755
1150
1000
1100
1000
FR14
NXP1500 6
1500
1650
1300
1950
2340
1500
1300
1500
1350
NXP1900 6
1900
2090
1500
2250
2700
1800
1500
2000
1500
NXP2250 6
(3)
2250
2475
1900
2782
3335
2000
1800
2300
2000
1
See
12.9.1 Overload Capability
2
The currents in given ambient temperatures are achieved only when the switching frequency is the same or smaller than the factory default.
3
Maximum ambient temperature +35 °C (+95 °F).
12.10 VACON® NXP IP00 Drive Modules Technical Data
Table 65: Technical Data
Technical item or function
Technical data
Connection of
mains
Input voltage U
in
380–500 V; 500–690 V; –10%…+10%
AQ351737303996en-000201 / DPD00888146 | Danfoss A/S © 2023.09
Specifications
VACON® NXP IP00 Drive Modules
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VACON NXP IP00 and is the answer not in the manual?

Danfoss VACON NXP IP00 Specifications

General IconGeneral
BrandDanfoss
ModelVACON NXP IP00
CategoryControl Unit
LanguageEnglish

Related product manuals