8.7.5.1 Saving Parameter Sets (Parameter Sets S6.3.1)
Use this function to get the factory default values back or save 1–2 customized parameter sets. A parameter set includes all parame-
ters of the application.
Procedure
In the Copy parameters (S6.3) subpage, find the Parameter sets (S6.3.1) with the Browser buttons.
Push the Menu button Right.
To go to the edit mode, push the Menu button Right.
The text LoadFactDef starts to blink.
There are 5 options to select from. Select the function with the Browser buttons.
Select LoadFactDef to download again the factory default values.
Select Store set 1 to save actual values of all parameters as set 1.
Select Load set 1 to download the values in set 1 as the actual values.
Select Store set 2 to save actual values of all parameters as set 2.
Select Load set 2 to download the values in set 2 as the actual values.
To accept the selection, push the [enter] button.
Wait until OK shows on the display.
8.7.5.2 Uploading Parameters to Control Panel (Up To Keypad, S6.3.2)
Use this function to upload all parameter groups to the control panel when the AC drive is stopped.
Procedure
In the Copy parameters (S6.3) subpage, find the Up to keypad page (S6.3.2).
Push the Menu button Right.
To go to the edit mode, push the Menu button Right.
All param. starts to blink.
To accept the selection, push the [enter] button.
Wait until OK shows on the display.
8.7.5.3 Downloading Parameters to Drive (Down From Keypad, S6.3.3)
Use this function to download 1 or all parameter groups from the control panel to an AC drive when the AC drive is stopped.
Procedure
In the Copy parameters (S6.3) subpage, find the Down from keypad page (S6.3.3).
Push the Menu button Right.
To go to the edit mode, push the Menu button Right.
Use the Browser buttons to select 1 of these 3 options:
All parameters (All param.)
All parameters but the motor nominal value parameters (All. no motor)
Application parameters
To accept the selection, push the [enter] button.
Wait until OK shows on the display.
8.7.5.4 Activating or Deactivating the Automatic Parameter Back-up (P6.3.4)
Use these instructions to activate or deactivate the parameter back-up.
When the application is changed, the parameters in the parameter settings on page S6.3.1 are deleted. To copy parameters from
one application to a different application, first upload them to the control panel.
AQ351737303996en-000201 / DPD0088898 | Danfoss A/S © 2023.09